Insulation Calculator: Thickness, Volume & Packs for a Target R-Value
Work out the insulation thickness for your target R-value or RSI, plus the volume and number of packs to buy for a loft, roof, wall or floor.
Metric mode uses square metres and RSI (m²K/W). Imperial mode uses square feet and the US R-value. Check the target for your climate and building code: lofts and roofs often need R-38 to R-60 (RSI 6.7 to 10.6), walls R-13 to R-21 (RSI 2.3 to 3.7). Pack coverage is printed on the pack.
Typical thermal conductivity (λ, W/mK): mineral wool 0.035, glass wool 0.040, EPS 0.038, XPS 0.034, PIR board 0.022, blown cellulose 0.040, closed-cell spray foam 0.025. Real products differ, so use the λ on the datasheet if you have it. Insulation squashed into a smaller space loses R-value.
About this tool
How much insulation do I need?
Insulation is sold by the pack but specified by R-value, so it is easy to buy too little or to pay for thickness you do not need. This calculator turns a target R-value into the thickness of the insulation, the volume, and the number of packs to buy for a loft, roof, wall or floor.
How to use it
- Choose metric (m², RSI) or imperial (ft², US R-value).
- Pick the material. Each one has a typical thermal conductivity (λ).
- Enter the area to insulate and the target R-value for your climate and building code.
- Enter the coverage printed on one pack and a waste allowance for cuts.
- Read the thickness needed, the thickness to buy, the R-value you will reach, the volume and the packs.
How the calculation works
The thermal resistance is the thickness divided by the conductivity, so the thickness is the RSI (m²K/W) multiplied by λ (W/mK). The US R-value is the RSI multiplied by 5.678. The result is rounded up to the next 10 mm (or 0.5 in) to give a thickness you can buy. The area plus the waste allowance is divided by the pack coverage and rounded up to give the number of packs.
Example
A 50 m² loft that needs RSI 6 with mineral wool (λ 0.035) needs 210 mm of insulation. With 10% waste the area is 55 m², the volume is 11.55 m³, and 5.76 m² packs mean 10 packs. In imperial units, 500 ft² at R-38 needs about 9.2 in of mineral wool, rounded up to 9.5 in.
FAQ
What R-value do I need?
It depends on your climate and local building rules. Lofts and roofs usually need the most, walls less. Check your local code or energy standard.
Is the pack thickness the same as the thickness I calculate?
Not always. Packs come in fixed thicknesses, and you can layer two to reach the total. Compare the thickness to buy with the product range.
Does compressing insulation reduce the R-value?
Yes. Squashing a batt into a thinner space lowers its R-value, so leave it fluffy and fill the full depth.